  Datasheet File OCR Text:
  cubefuse tm compact circuit protector base (ccpb) product description: the revolutionary bussmann ? series compact circuit protector base (ccpb) with bussmann series cubefuse? is designed as a fused branch circuit disconnect switch for the bussmann series quik-spec? coordination panelboard. the ccpb with cubefuse simplifies selective coordination and lockout/ tagout provisions allow for isolation of individual branch circuit loads for safe work practices. features and benefits: ? uses finger-safe, current-limiting bussmann series ul ? class cf cubefuse with class j performance available, time-delay or fast-acting versions from 1 to 100 amps* ? patented ampacity rejection feature helps prevent overfusing ? high 200ka short-circuit current ratings ? disconnect rated to provide means for load isolation ? all versions are full voltage rated at 600 vac ? 125vdc rated for 80 a and below ? ul 98 listed and suitable for branch circuit disconnect ? 1-, 2- and 3-pole versions are horsepower rated ? listed to ul and culus ? open fuse indication light per pole ? additional open fuse indication can be provided by using the time-delay indicating cubefuse version (6-100 a only) ? built-in switch/fuse interlock prohibits fuse removal while energized ? permanent lockout/tagout provisions ? lock-on provision available when used in the bussmann series quik-spec tm coordination panelboard (qscp) * see data sheet no. 9000 for time-delay cubefuse and data sheet no. 2147 for fast-acting cubefuse specifications. technical data 1161 effective april 2016 supersedes october 2015 bussmann series
2 specifcations: switch ampacity and rejection breaks ? 15, 20, 30, 40, 50, 60, 70, 90 and 100 a poles ? 1-, 2- and 3-pole versions volts ? 600vac (or less) ? 125vdc (15, 20, 30, 40, 70 and 90 a switches with 80 a fuse) agency information ? ul 98 listed, file e302370, guide whty ? culus to csa standard 22.2 no. 4, file e302370, guide whty7 ? ce ? rohs compliant terminals lineside bolt-on bus connector and torque ? bolt-mounted design into quik-spec coordination panelboard bus ? #10-32-unc hex flange phillips screw; 25 lb-in (2.8 n?m) loadside box lug terminal and torque ? 15-60a: ? 18 to 10awg (1 to 6mm 2 ) single or dual rated (same size wire), solid or stranded C 75c or higher - cu only; 20 lb-in (3.4 n?m) ? 8 to 6awg (10 to 16mm 2 ) single or dual rated (same size wire), solid or stranded C 75c or higher - cu only; 35 lb-in (5.8 n?m) ? 4awg (25mm 2 ) single C 75c or higher - cu only; 35 lb-in (5.8 n?m) ? 100a: ? 18 to 10awg (1 to 6mm 2 ) single, solid or stranded C 75c or higher - cu only; 25 lb-in (2.82 n?m) ? 8 to 1awg (10 to 45mm 2 ) single stranded C 75c or higher - cu only; 40 lb-in (4.52 n?m) ? 6awg (16mm 2 ) dual stranded (same size wire) C 75c or higher cu only; 45 lb-in (5.08 n?m) loadside fork terminal ? max. 30a suitable for use with #8-32unc screw lockout/tagout ? 4mm shank lock local open fuse indication ? light illumination requires closed circuit and minimum 90v operating voltage shipping weight ? 2.03 lbs per carton carton quantity ? 6 poles environmental data storage and operating temperature -20c to 75c** ** for fuse performance under or above 25c, consult fuse performance derating charts. switch handle lockout/tagout provision loadside spade terminal loadside box lug terminal local open fuse indication light lineside bolt-on bus connector switch on and off symbols cubefuse base 1-pole 2-pole 3-pole ccpb-1-_cf ccpb-2-_cf ccpb-3-_cf technical data1161 effective april 2016 cubefuse compact circuit protector base (ccpb) for quikCspec? coordination panelboards eaton.com/bussmannseries
3 catalog numbers: ccpb part numbers poles voltage rating accepts cubefuse amp range typical installed fuse amp range max. fuse amps ? sccr hp ratings (vac) ?? time-delay non-indicating time-delay indicating* fast-acting non-indicating** ccpb-1-15cf 1 600 vac, 125 vdc 1 to 15 tcf1rn, tcf3rn, tcf6rn, tcf10rn, tcf15rn tcf6, tcf10, tcf15 fcf1rn, fcf3rn, fcf6rn, fcf10rn, fcf15rn 15 a 200ka ac 100ka dc 0.5hp@120v ccpb-2-15cf 2 1.5hp@240v ccpb-3-15cf 3 600 vac 3hp@240v 5hp@480v 7.5hp@600v ccpb-1-20cf 1 600 vac, 125 vdc 1 to 20 tcf17-1/2rn, tcf20rn tcf17-1/2, tcf20 fcf20rn 20 a 200ka ac 100ka dc 0.75hp@120v ccpb-2-20cf 2 2hp@240v ccpb-3-20cf 3 600 vac 3hp@240v 7.5hp@480v 10hp@600v ccpb-1-30cf 1 600 vac, 125 vdc 1 to 30 tcf25rn, tcf30rn tcf25, tcf30 fcf25rn, fcf30rn 30 a 200ka ac 100ka dc 1.5hp@120v ccpb-2-30cf 2 3hp@240v ccpb-3-30cf 3 600 vac 5hp@240v 15hp@480v 10hp@600v ccpb-1-40cf 1 600 vac, 125 vdc 1 to 40 tcf35rn, tcf40rn tcf35, tcf40 fcf35rn, fcf40rn 40 a 200ka ac 100ka dc 2.0hp@120v ccpb-2-40cf 2 3hp@240v ccpb-3-40cf 3 600 vac 7.5hp@240v 20hp@480v 10hp@600v ccpb-1-50cf 1 600 vac 1 to 50 tcf45rn, tcf50rn tcf45, tcf50 fcf45rn, fcf50rn 50 a 200ka ac 100ka dc 3.0hp@120v ccpb-2-50cf 2 5hp@240v ccpb-3-50cf 3 600 vac 7.5hp@240v 20hp@480v 10hp@600v ccpb-1-60cf 1 600 vac 1 to 60 tcf60rn tcf60 fcf60rn 60 a 200ka ac 100ka dc 3.0hp@120v ccpb-2-60cf 2 7.5hp@240v ccpb-3-60cf 3 600 vac 7.5hp@240v 20hp@480v 10hp@600v ccpb-1-70cf 1 600 vac, 125 vdc 1 to 70 tcf70rn tcf70 fcf70rn 70 a 200ka ac 100ka dc 3.0hp@120v ccpb-2-70cf 2 7.5hp@240v ccpb-3-70cf 3 600 vac 15hp@240v 30hp@480v 40hp@600v ccpb-1-90cf 1 600 vac, 125 vdc ??? 1 to 90 tcf90rn tcf90 fcf80rn, fcf90rn 90 a 200ka ac 100ka dc 5.0hp@120v ccpb-2-90cf 2 10hp@240v ccpb-3-90cf 3 600 vac 20hp@240v 50hp@480v 40hp@600v CCPB-1-100CF 1 600 vac 1 to 100 tcf100rn tcf100 fcf100rn 100 a 200ka ac 5.0hp@120v ccpb-2-100cf 2 10hp@240v ccpb-3-100cf 3 20hp@240v 50hp@480v 40hp@600v * 1 a and 3 a indicating bussmann series cubefuse not available. correct fit with ccpb disconnect requires indicating bussmann series cubefuse with date code r38 or later. ** do not use ups/critical application fast-acting fcf with motors. ? any fuse with an amp rating less than or equal to the max fuse rating may be used. e.g., tcf15 may be used with ccpb-1-20cf. ?? indiacting or non-indicating time-delay bussmann series cubefuse only. ??? 125vdc only applies up to 80 a. technical data 1161 effective april 2016 cubefuse compact circuit protector base (ccpb) for quikCspec? coordination panelboards eaton.com/bussmannseries
4 dimensions in (mm): 15-60 a 70-100a for details on the ccpb and its use in the quik-spec coordination panelboard, see data sheet 1160. 1.0 (25.4) 2.0 (50.7) 3.0 (75.8) ?0.2 (5.08) 5.3 (133.3) 2.7 (69.6) 0.03 (0.84) 3.4 (86.0) 0.54 (13 72 ) 3.0 (75.8) 1.0 (25.4) 2.0 (50.7) (5.08) ?.2 2.7 (69.1) 2.9 3.9 (99.4) 0. 5 (12.9) (73.5) technical data1161 effective april 2016 cubefuse compact circuit protector base (ccpb) for quikCspec? coordination panelboards eaton.com/bussmannseries
5 motor sizing table: bussmann series low-peak? tcf_ and tcf_rn time-delay class cf fuses voltage motor size (hp) motor fla (amps) optimal protection (amps) code max (amps) heavy start (amps) 115vac, 1-phase 0.167 4.4 10 10 10 0.25 5.8 10 15 15 0.333 7. 2 15 15 15 0.5 9.8 15 20 20 0.75 13.8 25 25 30 1 16 25 30 35 1. 5 20 30 35 45 2 24 40 45 50 3 34 50 60 n/a 5** 56 90 100 n/a 230vac,1-phase 0.167 2.2 6 6 6 0.25 2.9 6 6 6 0.333 3.6 6 10 10 0.5 4.9 10 10 10 0.75 6.9 15 15 15 1 8 15 15 1 7. 5 1. 5 10 15 20 20 2 12 20 25 25 3 17 25 30 35 5 28 45 50 60 7. 5 40 60 n/a n/a 10** 50 80 90 n/a 200vac, 3-phase 0.5 2.5 6 6 6 0.75 3.7 6 10 10 1 4.8 10 10 10 1. 5 6.9 15 15 15 2 7. 8 15 15 1 7. 5 3 11 1 7. 5 20 20 5 1 7. 5 30 35 35 7. 5 25.3 40 45 50 20** 62.1 100 n/a n/a 208vac, 3-phase 0.5 2.4 6 6 6 0.75 3.5 6 10 10 1 4.6 10 10 10 1. 5 6.6 10 15 15 2 7. 5 15 15 15 3 10.6 1 7. 5 20 20 5 16.7 25 30 35 7. 5 24.2 40 45 50 20** 59.4 90 n/a n/a voltage motor size (hp) motor fla (amps) optimal protection (amps) code max (amps) heavy start (amps) 230vac, 3-phase 0.5 2.2 6 6 6 0.75 3.2 6 6 6 1 4.2 10 10 10 1. 5 6 10 15 15 2 6.8 15 15 15 3 9.6 15 20 20 5 15.2 25 30 30 7. 5 22 35 40 45 20** 54 90 100 n/a 460vac, 3-phase 0.5 1. 1 3 3 3 0.75 1. 6 3 3 3 1 2.1 6 6 6 1. 5 3 6 6 6 2 3.4 6 6 6 3 4.8 10 10 10 5 7. 6 15 15 15 7. 5 11 1 7. 5 20 20 10 14 25 25 30 15 21 35 40 45 20 27 40 50 60 50** 65 100 n/a n/a 575vac, 3-phase 0.5 0.9 3 3 3 0.75 1. 3 3 3 3 1 1. 7 3 3 3 1. 5 2.4 6 6 6 2 2.7 6 6 6 3 3.9 6 10 10 5 6.1 10 15 15 7. 5 9 15 20 20 10 11 1 7. 5 20 20 40** 41 70 80 80 note: use code max column for low to moderate reverse/jog/plug applications. * heavy start permitted only if code max does not allow motor start-up. based on motor fla from nec ? tables 430.248 and 430.250. technical data 1161 effective april 2016 cubefuse compact circuit protector base (ccpb) for quikCspec? coordination panelboards eaton.com/bussmannseries
the only controlled copy of this data sheet is the electronic read-only version located on the eaton network drive. all other copies of this document are by definition uncontrolled. this bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. eaton reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. eaton also reserves the right to change or update, without notice, any technical information contained in this bulletin. once a product has been selected, it should be tested by the user in all possible applications. eaton 1000 eaton boulevard cleveland, oh 44122 united states eaton.com bussmann division 114 old state road ellisville, mo 63021 united states eaton.com/bussmannseries ? 2016 eaton all rights reserved printed in usa publication no. 1161 C bu-sb15190 april 2016 for eatons bussmann series product information, call 1-855-287-7626 or visit: eaton.com/bussmannseries cubefuse compact circuit protector base (ccpb) for quikCspec? coordination panelboards technical data 1161 effective april 2016 eaton, bussmann, cubefuse, low-peak and quik-spec are valuable trademarks of eaton in the us and other countries. you are not permitted to use the eaton trademarks without prior written consent of eaton. csa is a registered trademark of the canadian standards group. nec is a registered trademark of the national fire protection association, inc. ul is a registered trademark of the underwriters laboratories, inc. follow us on social media to get the latest product and support information.


▲Up To Search▲   

 
Price & Availability of CCPB-1-100CF

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X